130/232
Building Technologies Boiler Sequence Controller RMK770 CE1P3132en
HVAC Products 7 Boiler control 23.04.2009
Number Text (as supplied) Effect
2344 [Boiler 4] underpressure Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
2345 [Boiler 5] underpressure Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
2346
[Boiler 6] underpressure Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
Number Text (as supplied) Effect
2351
[K1 valve] no checkback
signal
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 1
2352
[K2 valve] no checkback
signal
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 2
2353
[K3 valve] no checkback
signal
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 3
2354
[K4 valve] no checkback
signal
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 4
2355
[K5 valve] no checkback
signal
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 5
2356
[K6 valve] no checkback
signal
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 6
Number Text (as supplied) Effect
2361
[K1] flue gas overtem-
perature
Priority and effect can be parameterized.
Supply state: Nonurgent, no boiler stop,
must be acknowledged and reset
2362
[K2] flue gas overtem-
perature
Priority and effect can be parameterized.
Supply state: Nonurgent, no boiler stop,
must be acknowledged and reset
2363
[K3] flue gas overtem-
perature
Priority and effect can be parameterized.
Supply state: Nonurgent, no boiler stop,
must be acknowledged and reset
2364
[K4] flue gas overtem-
perature
Priority and effect can be parameterized.
Supply state: Nonurgent, no boiler stop,
must be acknowledged and reset
2365
[K5] flue gas overtem-
perature
Priority and effect can be parameterized.
Supply state: Nonurgent, no boiler stop,
must be acknowledged and reset
2366
[K6] flue gas overtem-
perature
Priority and effect can be parameterized.
Supply state: Nonurgent, no boiler stop,
must be acknowledged and reset
Fault checkback signal
shutoff valve
Flue gas temperature
limit exceeded