Building Technologies Boiler sequence controller RMK770 CE1P3132en
HVAC Products 7 Boiler control 23.04.2009
Number Text (as supplied) Effect
2401
[K1 pump] overload Nonurgent message; acknowledgement can
be parameterized; factory setting: “Acknowl-
edge“. No boiler stop
2402
[K2 pump] overload Nonurgent message; acknowledgement can
be parameterized; factory setting: “Acknowl-
edge“. No boiler stop
2403
[K3 pump] overload Nonurgent message; acknowledgement can
be parameterized; factory setting: “Acknowl-
edge“. No boiler stop
2404
[K4 pump] overload Nonurgent message; acknowledgement can
be parameterized; factory setting: “Acknowl-
edge“. No boiler stop
2405
[K5 pump] overload Nonurgent message; acknowledgement can
be parameterized; factory setting: “Acknowl-
edge“. No boiler stop
2406
[K6 pump] overload Nonurgent message; acknowledgement can
be parameterized; factory setting: “Acknowl-
edge“. No boiler stop
Number Text (as supplied) Effect
2411
[K1 pump] no flow Nonurgent message; must be acknowl-
edged and reset. No boiler stop
2412
[K2 pump] no flow Nonurgent message; must be acknowl-
edged and reset. No boiler stop
2413
[K3 pump] no flow Nonurgent message; must be acknowl-
edged and reset. No boiler stop
2414
[K4 pump] no flow Nonurgent message; must be acknowl-
edged and reset. No boiler stop
2415
[K5 pump] no flow Nonurgent message; must be acknowl-
edged and reset. No boiler stop
2416
[K6 pump] no flow Nonurgent message; must be acknowl-
edged and reset. No boiler stop
Number Text (as supplied) Effect
2421
[K1 pump B] overload Nonurgent message; acknowledgement can
be parameterized; factory setting: “Acknowl-
edge“. No boiler stop
2422
[K2 pump B] overload Nonurgent message; acknowledgement can
be parameterized; factory setting: “Acknowl-
edge“. No boiler stop
2423
[K3 pump B] overload Nonurgent message; acknowledgement can
be parameterized; factory setting: “Acknowl-
edge“. No boiler stop
2424
[K4 pump B] overload Nonurgent message; acknowledgement can
be parameterized; factory setting: “Acknowl-
edge“. No boiler stop
2425
[K5 pump B] overload
Nonurgent message; acknowledgement can
be parameterized; factory setting: “Acknowl-
edge“. No boiler stop
2426
[K6 pump B] overload
Nonurgent message; acknowledgement can
be parameterized; factory setting: “Acknowl-
edge“. No boiler stop
Overload boiler pump
Flow fault
boiler pump
Overload boiler pump B