Building Technologies Modular Heating Controller RMH760B CE1P3133en
HVAC Products 9 Heating circuit control 05.02.2007
The heating circuit can be configured to any type of module. If the RMZ782B is re-
placed by some other module, all settings using type reference RMZ782B… via “Extra
configuration“ must be reconfigured.
Function blocks can always be activated via “Extra configuration“, independent of the
type of plant. A function block is activated by assigning an output to a terminal. Here,
the heating circuit can be configured to any terminals that are free. If all outputs of the
heating circuit are set invalid, the heating circuit will be deactivated.
For weather-compensated heating circuit control, the outside temperature is required. It
can be configured as follows:
For heating circuit 1, on the following menu:
Main menu > Commissioning > Extra configuration > Miscellaneous > Inputs > Outside sensor
For the 2 other heating circuits, on the following menu:
Main menu > Commissioning > Extra configuration > Heating circuit 2 (or 3) > Inputs > Outside
sensor
The outside temperature can also be transmitted via the Konnex bus.
In addition, a solar intensity sensor and wind speed sensor for common usage by all
heating circuits can be configured on the following menu:
Main menu > Commissioning > Extra configuration > Miscellaneous > Inputs The impact on the
individual heating circuits can be parameterized.
For more detailed information, refer to section
14.6 “Weather data”.
Main menu > Commissioning > Extra configuration > Heating circuit 1 (or 2 or 3) > Inputs
Operating line
Adjustable values / display / remarks
Outside sensor*
Flow sensor
Room sensor
Return sensor Return temperature limitation
Room setpoint adjuster abs External room temperature setpoint adjuster
with absolute room temperature setpoints
Room setpoint adjuster rel External room temperature setpoint adjuster
with room temperature setpoint readjust-
ment of ±3 K
[Heating circuit pump] overload Fault input heating circuit pump
[Heat circuit pump B] overload Pump B in the case of twin pumps
Flow signal pump Flow supervision heating circuit pump(s)
Room operating mode External preselection
Timer function Comfort extension
Special day input
Holiday input
* Outside sensor:
Only heating circuits 2 and 3 have their own outside temperature. Heating circuit 1 shares the outside tem-
perature with other function blocks in the controller. The outside sensor is to be configured under
… > Miscel-
laneous > Inputs.
Main menu > Commissioning > Extra configuration > Heating circuit 1 (or 2 or 3) > Outputs
Operating line
Adjustable values / display / remarks
Outside temperature relay*
Mixing valve 3-pos
Mixing valve modulating
Heating circuit pump
Heating circuit pump B
Extra configuration
Outside sensor
Solar intensity and wind
speed sensor
Inputs
Outputs