Building Technologies Modular Heating Controller RMH760B CE1P3133en
HVAC Products 6 Boiler temperature control 05.02.2007
ErBu
PMinMon(Er3)
WLoLeDet(Er1)
BoPuEr
BuFb
TBo
BoPuEr_B
TRtBo
TFg
BoPu
BoPu_B
BuSt1
BuSt2
BuMdlt
BoSetpt
VlvShOff
VlvRtMx
PMaxMon(Er2)
BoPuErFlow
VlvShOffFb
3133S100
T
P
P
T
T
V
BoPu Boiler pump
BoPu_B Boiler pump B
BoPuEr
Fault input boiler pump
BoPuEr_B Fault input boiler pump B
BoPuErFlow Flow supervision boiler pump
BoSetpt Boiler temperature setpoint DC 0…10 V
BuFb Checkback signal burner stage 1
BuMdlt Modulating burner
BuSt1 Burner stage 1
BuSt2 Burner stage 2
WLoLeDet (Er1) Fault input 1 (water shortage)
PMaxMon (Er2) Fault input 2 (maximum pressure)
PMinMon (Er3) Fault input 3 (minimum pressure)
ErBu Fault input burner fault
TBo Boiler temperature sensor
TFg Flue gas temperature sensor
TRtBo Boiler return temperature sensor
VlvRtMx
Maintained boiler return temperature
VlvShOff Shutoff valve
VlvShOffFb Checkback signal shutoff valve
6.2 Configuration
The function block is activated in the factory for plant types H3-x and H4-x. Always
preconfigured is a boiler with a 1-stage burner, boiler pump, boiler temperature and
return temperature sensor. For plant types H4-x, a mixing valve with 3-position actuator
for the maintained boiler return temperature is also preconfigured.
For more detailed information, refer to section
3.2 “Basic configuration”.
Main menu > Commissioning > Basic configuration
Operating line Range Factory setting
Plant type H, H0-1…H6-7
Refer to subsection
3.2.1
Selecting the plant type“
H0-2
The basic configuration can be complemented and / or changed via “Extra configura-
tion”. Here, the 1-stage burner can be changed to become a 2-stage or modulating
burner, and shutoff valve, twin pump, flue gas temperature sensor and various check-
back signals and fault status signals can be added. Naturally, plant types H3-x can be
complemented by a mixing valve for the maintained boiler temperature.
Boiler diagram
Basic configuration
Extra configuration