EasyManua.ls Logo

Siemens Synco 700 - Settings on the Room Unit; DHW Data

Siemens Synco 700
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
210/238
Building Technologies Modular Heating Controller RMH760B CE1P3133en
HVAC Products 14 Communication 05.02.2007
If the time switch shall operate as a slave of a master time switch, the geographical
zone of the master time switch must be set here.
If that is the case, no more time switch data about the geographical zone will be for-
warded. But the geographical zone will still be required to ensure communication with the
room unit. The geographical zone must have a different setting value.
From the 2 settings, the following combinations are obtained:
Setting the geographical
zone (apartment)
Setting the time switch
slave (apartment)
Position of time switch
---- ----
Autonomous
1 (or more; max. 126)
----
Master
----
1 (or more; max. 126) Slave
1 (or more; max. 126) 1 (or more; max. 126) Slave
Main menu > Commissioning > Extra configuration > Heating circuit 1
(or 2 or 3)
Operating line Range Factory setting
Room control combination
Master /
Slave external setpoint /
Slave internal setpoint
Master
14.3.3 Settings on the room unit
The QAW740 is available as a digital room unit with communication facility. For com-
munication with the associated heating circuit, the same geographical zone and a
device address must be set on the room unit.
Also refer to Installation Instructions G1633 covering the QAW740.
14.4 DHW data
As with space heating, 2 or more DHW plants can be operated with one common time
switch.
Main menu > Commissioning > Communication > DHW
Operating line Range Factory setting
DHW zone 1…31
1
Time switch operation Autonomous / Master /
Slave
Autonomous
Time switch slave DHW
1…31 1
The settings made here are also displayed under:
Main menu > Device information > Communication > DHW
Here, the zone for DHW heating is to be set.
When using the
Master setting for time switch operation, the time switch data in the
DHW zone are forwarded for common usage.
DHW heating that shall make use of this time switch receives the settings.
Operating line Adjustable values / display / remarks
Time switch operation
Slave
Time switch slave DHW DHW zone of master
Several zones can be defined with one master.
Time switch slave
Combination choices
Extra configuration
Communication
DHW zone
Time switch operation and
time switch slave

Table of Contents