192/238
Building Technologies Modular Heating Controller RMH760B CE1P3133en
HVAC Products 12 Function block miscellaneous 05.02.2007
12.5 Display inputs
On the RMH760B, universal inputs can be defined for display purposes.
Main menu > Commissioning > Extra configuration > Miscellaneous > Inputs
Operating line
Adjustable values / display / remarks
Display input 1 Assign terminal
Display input 2 Assign terminal
Display input 3 Assign terminal
Display input 4 Assign terminal
The type or unit of the display input can be selected with the input identifier.
Main menu > Commissioning > Extra configuration > Miscellaneous > Input identifier
Operating line Range Factory setting
Display input 1
°C / % / g/kg / kJ/kg /
W/m2 / m/s / bar /
mbar / Pa / ppm /
Universal 000.0 /
Universal 0000 /
Digital
°C
Display input 2 Same as display input 1
°C
Display input 3
Same as display input 1
°C
Display input 4
Same as display input 1
°C
For other setting choices, such as resolution, type of sensor, etc., refer to subsection
3.3.2 “Configuration of the universal inputs and outputs“.
Main menu > Commissioning > Settings > … or
Main menu > Settings > Inputs > …X…
Operating line Range Factory setting
Type
Ni1000 / 2xNi1000 / T1 /
Pt1000 / DC 0…10 V
Ni1000
Value low Depending on the se-
lected type
Depending on the
type
Value high Depending on the se-
lected type
Depending on the
type
Correction − 3.0…3.0 K 0.0 K
Normal position Open / Closed Open
The type only appears with analog inputs, the normal position only with the digital
inputs.
Value low and value high as well as corrections only appear with designations and
types that support these settings.
For detailed information about the configuration of analog inputs, refer to subsection
3.3.2 “Configuration of the universal inputs and outputs”.
The fault inputs can be assigned free text.
Main menu > Commissioning > Settings > … or
Main menu > Settings > Texts
Operating line Range Factory setting
Display input 1 Max. 20 characters
Display input 2 Max. 20 characters
Display input 3 Max. 20 characters
Display input 4 Max. 20 characters
Configuration
Input identifier
Other settings