Building Technologies Modular Heating Controller RMH760B CE1P3133en
HVAC Products 6 Boiler temperature control 05.02.2007
6.11 Fault handling
Number Text Effect
40 Boiler sensor error
Urgent message; must be acknowledged.
No boiler stop; the burner is shut down
41 Boiler return sensor error
Nonurgent message; must be acknowl-
edged. No boiler stop
In the case of plant with mixing valve for
the maintained boiler return temperature,
the mixing valve will be driven to the fully
closed position when the return tempera-
ture sensor is faulty and then deenergized
to make possible manual adjustment.
Otherwise, the control system behaves like
a plant without return temperature sensor
321
Flue gas temp sensor error Nonurgent message; must be acknowl-
edged. No boiler stop
Number Text Effect
2301
Boiler burner fault Urgent message.
Acknowledgement can be parameterized;
factory setting: “Acknowledge”.
Boiler stop
2311
Burner no checkback signal Urgent message; must be acknowledged
and reset. Effect can be parameterized;
factory setting: “Stop”. Boiler stop
Number Text Effect
2321
Boiler water shortage Priority, effect and acknowledgement can
be parameterized.
Factory setting: “Urgent”. Boiler stop, must
be acknowledged
2331
Boiler overpressure Priority, effect and acknowledgement can
be parameterized.
Factory setting: “Urgent”. Boiler stop, must
be acknowledged
2341
Boiler underpressure Priority, effect and acknowledgement can
be parameterized.
Factory setting: “Urgent”. Boiler stop, must
be acknowledged
2351
Shutoff valve no checkb
signal
Urgent message; must be acknowledged
and reset. Boiler stop
2361
Flue gas overtemperature Priority and effect can be parameterized.
Factory setting: “Nonurgent”. No boiler
stop, must be acknowledged and reset
Number Text Effect
2401 [Boiler pump] overload
Nonurgent message.
Acknowledgement can be parameterized;
factory setting: “Acknowledge and reset“.
No boiler stop
Sensor error
Burner faults
Boiler faults
Faults of the boiler pump

Table of Contents

Other manuals for Siemens Synco 700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Synco 700 and is the answer not in the manual?

Siemens Synco 700 Specifications

General IconGeneral
BrandSiemens
ModelSynco 700
CategoryController
LanguageEnglish

Related product manuals