125/238
Building Technologies Modular Heating Controller RMH760B CE1P3133en
HVAC Products 9 Heating circuit control 05.02.2007
0
5
10
15
20
25
TOstrDmp
TOeff
t
3131D23
TO
TO
Main menu > Commissioning > Settings > … or
Main menu > Settings > Heating circuit 1 (or 2 or 3) > Space heating
Operating line Range Factory setting
Building time constant
0…200 h 20 h
Main menu > Heating circuit 1 (or 2 or 3) > Heating curve
Operating line Range Factory setting
Proportion of windows
0…100 % 50 %
9.5.2 Heating curve
The heating curve is defined by 2 curvepoints:
1
:
At the design temperature
• By the outside temperature TODef
A
• By the flow temperature SetPTFlDef
B
2 :
At the theoretical heating limit
• By the outside temperature TOHi
C
• By the flow temperature SetPTFlHi
D
SetPTFlDe
SetPTFlHi
SetPTRN
TFl
TOeff
TODe
sHC
TOHi
B
D
A
C
1
2
3131 D24
The nonlinear heat transmission is considered by the radiator exponent nH. The follow-
ing table gives an overview of the different types of heating systems normally used:
Heat transmission via… Radiator exponent nH
Underfloor heating system 1.05…1.1
Flat radiators 1.26…1.33
Radiators to DIN 4703 1.3
Convectors 1.25…1.45