Building Technologies Modular Heating Controller RMH760B CE1P3133en
HVAC Products 9 Heating circuit control 05.02.2007
0
5
10
15
20
25
TOstrDmp
TOeff
t
3131D23
TO
TO
Main menu > Commissioning > Settings > … or
Main menu > Settings > Heating circuit 1 (or 2 or 3) > Space heating
Operating line Range Factory setting
Building time constant
0…200 h 20 h
Main menu > Heating circuit 1 (or 2 or 3) > Heating curve
Operating line Range Factory setting
Proportion of windows
0…100 % 50 %
9.5.2 Heating curve
The heating curve is defined by 2 curvepoints:
1
:
At the design temperature
• By the outside temperature TODef
A
• By the flow temperature SetPTFlDef
B
2 :
At the theoretical heating limit
• By the outside temperature TOHi
C
• By the flow temperature SetPTFlHi
D
SetPTFlDe
SetPTFlHi
SetPTRN
TFl
TOeff
TODe
sHC
TOHi
B
D
A
C
1
2
3131 D24
The nonlinear heat transmission is considered by the radiator exponent nH. The follow-
ing table gives an overview of the different types of heating systems normally used:
Heat transmission via… Radiator exponent nH
Underfloor heating system 1.05…1.1
Flat radiators 1.26…1.33
Radiators to DIN 4703 1.3
Convectors 1.25…1.45
Settings
Heating curve
Curvepoints
Radiator exponent

Table of Contents

Other manuals for Siemens Synco 700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Synco 700 and is the answer not in the manual?

Siemens Synco 700 Specifications

General IconGeneral
BrandSiemens
ModelSynco 700
CategoryController
LanguageEnglish

Related product manuals