Building Technologies Modular Heating Controller RMH760B CE1P3133en
HVAC Products 12 Function block miscellaneous 05.02.2007
12.3.2 Fault handling
When leaving the “Commissioning“ menu, a check is made to see if the outside sensor
is connected or a sensor value is received via bus. If there is no outside temperature, or
in the case of a short-circuit, fault status message “Outside temp sensor error“ will
appear. Internally, the controller continues to operate using 0 °C as a backup value.
If outside temperatures from other outside temperature zones are available via bus,
they will be used as backup values until the error has been rectified.
Only one outside temperature may be present in the same zone. If several controllers
transmit their outside temperature in the same zone, fault status message “>1 outside
temp sensor HC 1“ (or HC 2 or HC 3) will be delivered.
Number Text Effect
10
Outside temp sensor error 1 Nonurgent message; must not be ac-
knowledged
13
Outside temp sensor error 2 Nonurgent message; must not be ac-
knowledged
16
Outside temp sensor error 3 Nonurgent message; must not be ac-
knowledged
11
>1 outside temp sensor HC 1 Urgent message; must be acknowl-
edged.
More than one outside sensor in the
same outside temperature zone.
14
>1 outside temp sensor HC 2 Urgent message; must be acknowl-
edged.
More than one outside sensor in the
same outside temperature zone.
17
>1 outside temp sensor HC 3 Urgent message; must be acknowl-
edged.
More than one outside sensor in the
same outside temperature zone.
12
Outside sensor 1 simul active Nonurgent message; must not be ac-
knowledged
15
Outside sensor 2 simul active Nonurgent message; must not be ac-
knowledged
18
Outside sensor 3 simulation
active
Nonurgent message; must not be ac-
knowledged
20
Solar intensity sensor error
Solar intensity sensor not connected
Bus communication interrupted
Solar zone not correctly set (transmit-
ter and receiver must use the same
solar zone)
Nonurgent message; must not be ac-
knowledged
21
>1 solar intensity sens in
zone
More than one solar intensity sensor in
the same solar zone.
Urgent message; must be acknowledged
30
Wind speed sensor error
Wind speed sensor not connected
Bus communication interrupted
Wind zone not correctly set (transmit-
ter and receiver must use the same
wind zone)
Nonurgent message; must not be ac-
knowledged