HVAC Products 5 General functions, fundamentals 05.02.2007
Main menu > Commissioning > Communication > Heating circuit 1 (or 2 or 3)
Operating line Range Factory setting
Geographical zone (apartm.) ---- / 1…126
----
Time switch slave (apartm.)
---- / 1…126 ----
Main menu > Commissioning > Communication > DHW
Operating line Range Factory setting
DHW zone 1…31 1
Time switch operation
Autonomous / Slave /
Master
Autonomous
Time switch slave DHW 1…31 1
For details on settings regarding time switch communication, refer to chapter 14
”
Communication“.
5.1.2 Entries
For space heating, a specific 24-hour program can be selected for each day:
Main menu > Heating circuit 1 (or 2 or 3) > Time switch 1 (or 2 or 3 )
Operating line Range Factory setting
Monday
Comfort / Precomfort /
Economy
From 06:00 Com-
fort / From 22:00
Economy
up to
Sunday
Comfort / Precomfort /
Economy
From 06:00 Com-
fort / From 22:00
Economy
Special day
Comfort / Precomfort /
Economy
From 06:00 Com-
fort / From 22:00
Economy
The times are to be entered with the help of a display (using indicator
):
Tuesday
From Comfort
For DHW heating, a specific 24-hour program can be selected for each day:
Main menu > DHW > DHW time switch
Operating line Range Factory setting
Monday
Normal / Reduced From 05:00 Nor-
mal
From 22:00 Re-
duced
up to
Sunday Normal / Reduced From 05:00 Nor-
mal
From 22:00 Re-
duced
Space heating
Note
DHW heating