Building Technologies Modular Heating Controller RMH760B CE1P3133en
HVAC Products 9 Heating circuit control 05.02.2007
Operating line Range Factory setting
Actuator running time
1…600 s 150 s
P-band Xp
1…100 K 50 K
Integral action time Tn
0…600 s 60 s
For more detailed information about mixing valve control and its setting aids, refer to
section
5.7 “Mixing valve control”.
9.6.2 Load control
The heat output of mixing valve control can be reduced by functions of higher priority
(e.g. by return temperature limitation) or by functions of other plants (boiler, DHW
heating). This is accomplished via load control.
T
T
3131B15
T
Heat
consumer
Heat
source
Heat
consumer
Heat demand
Load control
Load reduction can be triggered by one of the following functions:
Protective boiler startup
Limitation of the return temperature
DHW heating with shifting priority
DHW heating with absolute priority
From the consumer's point of view, a load increase can be effected in the form of pump
and / or mixing valve overrun. In principle, this means load maintenance.
9.7 Optimization functions
The opimization functions are activated or influenced by the following settings:
Main menu > Commissioning > Settings > … or
Main menu > Settings > Heating circuit 1 (or 2 or 3) > Optimizations/influences
Operating line Range Factory setting
Type of optimization With room model /
With room temp sensor
With room model
Forward shift on max 0…48 h 0 h
Early shutdown max 00.00…06.00 h.min 00:00 h.min
Quick setback Off / On On
[Boost heating] setpoint increase 0…20 K 5 K
Room temperature rise
1…600 min/K 60 min/K
Load reduction
Load increase
Settings