Building Technologies Modular Heating Controller RMH760B CE1P3133en
HVAC Products 11 Function block meter 05.02.2007
11 Function block meter
11.1 Overview of function block
iiii
1
2
3
4
Counter
i 1
Meter input 1
i 2
Meter input 2
i 3
Meter input 3
i 4
Meter input 4
11.2 Configuration
The meters are to be activated via “Extra configuration” by assigning a terminal to the
meter input.
Main menu > Commissioning > Extra configuration > Data acquisition > Meter 1 (or 2, 3 or 4)
Operating line Range Factory setting
Input 1 (etc., through Input 4) --- / RMH760.X3, etc. ---
Displayed unit Wh / kWh / MWh /
kJ / MJ / GJ /
ml / l / m3 /
Heat cost unit /
No unit / BTU
kWh
Displayed format 0 / 0.0 / 0.00 / 0.000 0
The unit shown can be selected via datapoint
Displayed unit.
Datapoint
Displayed format defines the number of decimal places.
11.3 Types of meters
The meters are used to acquire consumption values.
Pulses from the following types of meters can be handled:
Gas meters
Hot water meters
Cold water meters
Electricity meters
The pulse values represent:
Energy in kJ, MJ, GJ, Wh, kWh and MWh
Volume in m
3
, l
or ml
Variables with no unit (max. 3 decimal places)
Heat cost unit
BTU (British Thermal Unit)
The pulses are converted to consumption values according to the setting values and
then added; the cumulated values are stored as 15-month values at midnight when the
month changes. The monthly values of the last 15 months will be stored.