90/238
Building Technologies Modular Heating Controller RMH760B CE1P3133en
HVAC Products 6 Boiler temperature control 05.02.2007
Number Text Effect
2411
[Boiler pump] no flow Nonurgent message; must be acknowl-
edged and reset. No boiler stop
2421
[Boiler pump B] overload Nonurgent message.
Acknowledgement can be parameterized.
Factory setting: “Acknowledge and reset“.
No boiler stop
2431
[Main pump B] no flow Nonurgent message; must be acknowl-
edged and reset. No boiler stop
2441
[Boiler pump] fault Urgent message; must not be acknowl-
edged. Boiler stop
6.12 Text for boiler designation
Main menu > Commissioning > Settings > …
Main menu > Settings > Boiler
Operating line Range Factory setting
Boiler Max. 20 characters Boiler
If required, specific text can be used to designate the boiler. This text will then appear
on the menu and on the info display.
6.13 Diagnostic choices
Main menu > Boiler > Inputs/setpoints
Operating line Adjustable values / display / remarks
Release input
Actual value boiler temperature
Boiler temperature setpoint
Actual value return temp
Return temperature min
Checkb sign shutoff valve
[Boiler pump] overload
[Boiler pump B] overload
Flow signal pump
Fault burner
Checkback signal burner
Burner hours run
Burner start counter
Flue gas temperature
Flue gas temperature maximum
Flue gas temperature limit value
Flue gas meas mode contact
Fault text
Fault text for fault input 1
Fault input 1
Fault text
Fault text for fault input 2
Fault input 2
Fault text
Fault text for fault input 3
Fault input 3
Attenuated outside temp
Inputs/setpoints