Building Technologies Modular Heating Controller RMH760B CE1P3133en
HVAC Products 6 Boiler temperature control 05.02.2007
Main menu > Commissioning > Settings > … or
Main menu > Settings > Boiler > Fault settings > Fault input 2
Operating line Range Factory setting
Fault settings
Max. 20 characters
Overpressure
Impact of fault
No stop / Stop
Stop
Fault acknowledgement None / Acknowledge /
Acknowledge and reset
Acknowledge
Fault priority Urgent / Not urgent Urgent
Fault status message delay 00.00…59.55 m.s 00.05 m.s
Main menu > Commissioning > Settings > … or
Main menu > Settings > Boiler > Fault settings > Fault input 3
Operating line Range Factory setting
Fault settings Max. 20 characters Underpressure
Impact of fault No stop / Stop Stop
Fault acknowledgement None / Acknowledge /
Acknowledge and reset
Acknowledge
Fault priority Urgent / Not urgent Urgent
Fault status message delay 00.00…59.55 m.s 00.05 m.s
Main menu > Commissioning > Settings > … or
Main menu > Settings > Boiler > Fault settings > Flue temp supervision
Operating line Range Factory setting
Flue gas temperature limit value ---- / 8…400 °C ---- °C
Impact of fault No stop / Stop No stop
Fault priority Urgent / Not urgent Nonurgent
6.10 Burner hours run counter and burner start
counter
For burner stage 1 or the burner’s basic stage, a checkback signal can be configured.
In addition to burner supervision, this checkback signal is used for the burner hours run
counter and the burner start counter.
When there is no checkback signal, the burner hours run counter is started by the
output relay for burner stage 1.
Main menu > Commissioning > Extra configuration > Boiler > Inputs
Operating line Adjustable values / display / remarks
Checkback signal burner Assign input
The number of burner hours run and the number of burner starts are shown on the
“Inputs/setpoints“ menu. On the user level, they can only be read, on the service level,
they can also be readjusted. It is thus possible to set the effective values.
or Main menu > Boiler > Inputs/setpoints
Operating line Range Factory setting
Burner hours run 0…99999 h 0 h
Burner start counter 0…99999 0