117/238
Building Technologies Modular Heating Controller RMH760B CE1P3133en
HVAC Products 9 Heating circuit control 05.02.2007
Forwarding the resulting room operating mode from the Qx relay outputs of the
RMH760B to a Synco™200 controller:
G
G0
AC 24 V
G
G0
MD1
N2
3121A05
G
G0
N1
Qx3
Qx4
Qx3
Qx4
MD2
N1 RMH760B
N2 Synco™200 RLU2…
Main menu > Commissioning > Extra configuration > Heating circuit 1
(or 2 or 3) > Outputs
Operating line Adjustable values / display / remarks
Operating mode relay 1 --- / N.Q1…, etc. (only free relays) /
assignment of operating mode relays
Operating mode relay 2 --- / N.Q1…, etc. (only free relays) /
assignment of operating mode relays
On the “Settings” menu, the operating mode relay to be energized can be defined for
each room operating mode.
Main menu > Settings > Heating circuit 1
(or 2 or 3) > Space heating
Operating line Range Factory setting
Comfort relay control
--- / R1 / R2 / R1+R2 ---
Precomfort relay control
--- / R1 / R2 / R1+R2 ---
Economy relay control
--- / R1 / R2 / R1+R2 R2
Protection relay control
--- / R1 / R2 / R1+R2 R1+R2
The factory setting has been chosen such that the digital outputs can be connected
directly to the digital inputs of the Synco™200 controller.
Since the Synco™200 controllers do not use the Precomfort mode, an automatic
change from Precomfort to Comfort mode will be made. This setting can be changed to
suit individual needs.
The adjustable values previously listed under "Settings" have the following meaning:
Value set
State of relay R1
State of relay R2
---
Normal position Normal position
R1 Operating position Normal position
R2 Normal position Operating position
R1+R2 Operating position
Operating position
The
Outputs menu shows the state of the operating mode relays:
Main menu > Heating circuit 1 (or 2 or 3) > Outputs
Operating line Current state
Operating mode relay 1 Off or On
Operating mode relay 2 Off or On
pplication example
Configuration of both
operating mode relays
Settings
Note on factory setting
Meaning of
adjustable values
Display values