216/238
Building Technologies Modular Heating Controller RMH760B CE1P3133en
HVAC Products 14 Communication 05.02.2007
Number Text Effect
5402
>1 identical geogr zone [1] More than one room master for plant 1 in
the same geographical zone.
Nonurgent message; must be acknowl-
edged
Number Text Effect
5411
Room master failure in HC 2
Room master for the room control combi-
nation for plant 2 is missing or cannot be
received.
Nonurgent message; must not be ac-
knowledged
5412
>1 identical geogr zone [2]
More than one room master for plant 2 in
the same geographical zone.
Nonurgent message; must be acknowl-
edged
Number Text Effect
5421
Room master failure in HC 3 Room master for the room control combi-
nation for plant 3 is missing or cannot be
received.
Nonurgent message; must not be ac-
knowledged
5422
>1 same geogr zone [3] More than one room master for plant 3 in
the same geographical zone.
Nonurgent message; must be acknowl-
edged
Number Text Effect
6001 >1 identical device address
More than one controller with the same
device address.
Urgent message; must be acknowledged
Room master and zone
error in heating circuit 2
Room master and zone
error in heating circuit 3
ddressing error