TXP CLC Course
EUZE
This parameter defines the delay time on triggering of the input range monitoring
function when a delay has been specified for parameter EU as in options 2, 5, 6,
7, and 8. The range of values that can be used are 0.25 to 60s
The default setting is 1s
EAS
This parameter defines which signal is to be processed further in the event of a
channel fault. There are 3 possible choices in the parameter mask: 0 – 2.
Meaning:
0 = Do not process substitution signal
1 = Process last valid analog value
2 = Process value from EASW parameter
The default setting is 0
LRV
This parameter defines the physical lower limit value of the input signal related to
an input of 4 mA.
URV
This parameter defines the physical upper limit value of the input signal related to
an input of 20 mA.
UNIT
This parameter defines the engineering units of the input signal.
GSB1
This parameter defines whether limit signal 1 is active or not. There are 2
possible choices in the parameter mask: 0 and 1 where 0 = off and 1 = on.
GSB2
This parameter defines whether limit signal 2 is active or not. There are 2
possible choices in the parameter mask: 0 and 1 where 0 = off and 1 = on.
GSB3
This parameter defines whether limit signal 3 is active or not. There are 2
possible choices in the parameter mask: 0 and 1 where 0 = off and 1 = on.
GSB4
This parameter defines whether limit signal 4 is active or not. There are 2
possible choices in the parameter mask: 0 and 1 where 0 = off and 1 = on.