TXP CLC Course
EGSW4
This parameter defines the substitution value of limit signal 4 (GS4) that will be
processed further in the event of a channel fault (only applicable when parameter
EGS4 is set to ”1”). There are 2 possible choices in the parameter mask: 0 and 1.
Meaning:
0 = substitution limit signal = 0
1 = substitution limit signal = 1
The default setting is 0
EGS1
This parameter defines whether a substitution limit signal is to be generated for
limit signal 1(GS1) in the event of a channel fault. There are 2 possible choices in
the parameter mask: 0 and 1. Meaning:
0 = do not use substitution limit signal
1 = do use substitution limit signal
The default setting is 0
EGS2
This parameter defines whether a substitution limit signal is to be generated for
limit signal 2 (GS2) in the event of a channel fault. There are 2 possible choices
in the parameter mask: 0 and 1. Meaning:
0 = do not use substitution limit signal
1 = do use substitution limit signal
The default setting is 0
EGS3
This parameter defines whether a substitution limit signal is to be generated for
limit signal 3 (GS3) in the event of a channel fault. There are 2 possible choices
in the parameter mask: 0 and 1. Meaning:
0 = do not use substitution limit signal
1 = do use substitution limit signal
The default setting is 0
EGS4
This parameter defines whether a substitution limit signal is to be generated for
limit signal 4 (GS4) in the event of a channel fault. There are 2 possible choices
in the parameter mask: 0 and 1. Meaning:
0 = do not use substitution limit signal
1 = do use substitution limit signal
The default setting is 0
Training Center
Copying of this document, and giving it to others and use or communication of the contents, are forbidden without express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.
10