TXP CLC Course
Group Alarm Acknowledgement (SQ)
Allows FB 163 DCM block to acknowledges all active alarms and return to
normal condition for the block when the logic input is a binary “1”.
Block OM operating (BL/OM)
Disables operation from Super ordinate System (OM650) when the input is a
binary “1”. Does not allow manual operations including alarm acknowledge,
operator required actions, manual on, manual off, changeover operation mode
(manual, semiautomatic or automatic) or tag-out.
Block alarm protection command (BL/AP)
When this input is a binary “1” an executed protection command does not
need to be acknowledged.
A protection command execution with BL/AP causes the following:
Last status reached by protection is set
Feed back message shows actual state (on or off)
Disables the respective counter command
A protection command execution without BL/AP causes the following:
NOSD (no status discrepancy or message at protection execution) is reset
Last status reached by protection is set
Feed back message shows actual state (on or off)
Disables the respective counter command
Icon on OM650 flashes red at 2HZ
Acknowledgement of “O” class alarm in mini ASD is required by operator
Auto command on (A/ON)
When this input is a binary “1” and the DCM is in semi or auto operation mode,
and the input EN/ON is a binary 1; the output ALE is activated.
Auto command off (A/OFF)
When this input is a binary “1” and the DCM is in semi or auto operation mode,
and the input EN/ON is a binary 1; the output ALA is activated.
Under voltage limit signal (UGS)
When this input is a binary “1” the maximum under voltage timer TUM is started.
Protection command on (P/ON)
When this input is a binary “1” the DCM is forced on (ALE on) regardless of state
of the enabling inputs
Protection command off (P/OFF)
When this input is a binary “1” the DCM is forced off (ALA off) regardless of the
state of the enabling inputs