EasyManua.ls Logo

Siemens TXP-CLC - Serial Number Assignments for MIN and MAX

Siemens TXP-CLC
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TXP CLC Course
5
Serial number assignments for MIN and MAX
MIN signals are generated from set points below a median value of an analog
signal range. MAX signals are generated from set points above the median of an
analog signal range. To separate between MIN and MAX signals the following
rules apply:
MIN even serial numbers
NOC = 02, 04, ... 48
NCC = 52, 54, ... 98
MAX odd serial numbers
NOC = 01, 03, ... 49
NCC = 51, 53, ... 99
For a switching device that has both a NOC and a NCC, (changeover contacts),
the serial numbers would be assigned with a difference of 50 between them, i.e.
XG01 - XG51 or XG02 - XG52.
Training Center
Copying of this document, and giving it to others and use or communication of the contents, are forbidden without express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.
25

Table of Contents

Related product manuals