TXP CLC Course
11
Command direction priority (PBR)
Name: PBR
Function: Defines the priority of the command direction to determine if the Off
command (ALE) will override the On command (ALA) when both are selected.
Range of values: cmd. priority: off / on
cmd. priority: on / off
Basic setting: cmd. priority: off / on
Command output versions (BAV)
Name: BAV
Function: Defines command output (ALE & ALA) as permanent for latching in the
control system and reversing logic of command output (inversion) for normally
open or fail open valves.
Range of values: pers.cmd:N -- inv.:N -- RT.err--reset:N
pers.cmd:Y -- inv.:N -- RT.err--reset:N
pers.cmd:N -- inv.:Y -- RT.err--reset:N
pers.cmd:Y -- inv.:Y -- RT.err--reset:N
pers.cmd:N -- inv.:N -- RT.err--reset:Y
pers.cmd:Y -- inv.:Y -- RT.err--reset:Y
Basic setting: pers.cmd:N -- inv.:N -- RT.err--reset:N
Meaning:
Persistent
command
& Inversion & Run-time disconnection
No No No
Yes No No
No Yes No
Yes Yes No
No No Yes
irrelevant irrelevant irrelevant
Yes No Yes
irrelevant irrelevant irrelevant
Max. under voltage time (TUM)
Name: TUM
Function: Defines the max. permissible voltage failure time for automatic
restarting.
Range of values: 0 to 10,000
Meaning: 0 = 0 s (no restart)
10,000 = 1,000 s (adjusting steps: 0.1 s)
Basic setting: 0