MIN limit value
For a MIN limit value the switching point is obtained by changing the measured
variable in relation to a minimum value, i.e. < MIN. For the MIN limit value the
< MIN signal is derived from the NCC of the switching device. Figure 8 and 9
show examples of < MIN signals for pressure and level. The < MIN signals are
assigned serial numbers of XG52 and NOT MIN signals are assigned serial
numbers of XG02.
MIN NOT MIN
XG52 XG02 XG52 XG02
50 100
PSIG PSIG
Pressure Pressure
NCC NOC NCC NOC
Set-point Set-point
75 PSIG 75 PSIG
Pressure MIN Pressure NOT MIN or > MIN
Figure 8 - MIN Signal (Pressure) - XG52/XG02
MIN NOT MIN
XG52 XG02 XG52 XG02
Level Level
NCC NOC NCC NOC
Level MIN Level NOT MIN or > MIN
Figure 9 - MIN Signal (Level) - XG52/XG02