TXP CLC Course
12
CP 1430
1. Obtain MAC-addresses
• Open the YDH-drawing.
• Click on the symbol of the CP1430 you want to change.
• Open the module properties.
• Read the MAC-addresses. Address 1 is for the upper rack, address 2 for
the lower rack.
2. Initialize CP1430
• Hook up the PG740 to the CP1430
• Start the S5-software
• In the main menu line: select: “Change->further”
• Select the directory COM1430, if not already selected
• Select SINEC NCM COMs in this directory
• Select “CP-Functions->Stop” from the main menu line. The “Stop”-light at
the CP should go on
• Select “Edit->CP Init” from the main menu line. Editing of the fields should
be possible
• Enter the MAC-address and the Basis SSNR (232 for the upper rack (AP
A), 236 for the lower rack (AP B)) and hit F7 (ok)
• Select “CP-Functions->Start” from the main menu line. The “Stop”-light at
the CP should go off (if there is code in the CPU) and the “Run” light
should go on
• Select “Utilities” then “Clock Functions”
• Press F2 to set time. Enter the current date and time (Winter time of the
local time zone must be set; date is in DDMMYY format)