TXP-CLC Course
8
ULLL1
This parameter defines the triggering direction of limit value 1. There are 2
possible choices in the parameter mask: 0 and 1 where 0 = lower limit trigger and
1 = upper limit trigger.
ULLL2
This parameter defines the triggering direction of limit value 2. There are 2
possible choices in the parameter mask: 0 and 1 where 0 = lower limit trigger and
1 = upper limit trigger.
ULLL3
This parameter defines the triggering direction of limit value 3. There are 2
possible choices in the parameter mask: 0 and 1 where 0 = lower limit trigger and
1 = upper limit trigger.
ULLL4
This parameter defines the triggering direction of limit value 4. There are 2
possible choices in the parameter mask: 0 and 1 where 0 = lower limit trigger and
1 = upper limit trigger.
EGSW1
This parameter defines the substitution value of limit signal 1 (GS1) that will be
processed further in the event of a channel fault (only applicable when parameter
EGS1 is set to ”1”). There are 2 possible choices in the parameter mask: 0 and 1.
Meaning:
0 = substitution limit signal = 0
1 = substitution limit signal = 1
The default setting is 0
EGSW2
This parameter defines the substitution value of limit signal 2 (GS2) that will be
processed further in the event of a channel fault (only applicable when parameter
EGS2 is set to ”1”). There are 2 possible choices in the parameter mask: 0 and 1.
Meaning:
0 = substitution limit signal = 0
1 = substitution limit signal = 1
The default setting is 0
EGSW3
This parameter defines the substitution value of limit signal 3 (GS3) that will be
processed further in the event of a channel fault (only applicable when parameter
EGS3 is set to ”1”). There are 2 possible choices in the parameter mask: 0 and 1.
Meaning:
0 = substitution limit signal = 0
1 = substitution limit signal = 1 The default setting is 0