EasyManua.ls Logo

Siemens TXP-CLC - Reject to Manual (REJ;MAN); Operation Mode (OP_MODE); Behavior on Switchgear Fault (BSFG); Inputs from Other Logic (Not I;O Type Inputs)

Siemens TXP-CLC
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TXP CLC Course
11
Reject to manual (REJ/MAN)
Name: REJ/MAN
Function: Defines whether the operation mode set to manual in the event of a
fault or failure. Can only be activated by enabling TAG-OUT via parameter RMS.
Range of values: Not activated / activated
Basic setting: Not activated.
Operation mode (OP_MODE)
Name: OP_MODE
Function: Defines the possible operating modes. Can only be activated by
enabling TAG-OUT via parameter RMS.
Range of values: AUTO / MAN
SEMI
SEMI / MAN
Basic setting: AUTO / MAN.
Behavior on switchgear fault (BSFG)
Name: BSFG
Function: Defines whether it is possible to initiate a manual “OFF” command from
OM650 while the switchgear, breaker or motor starter is in fault (SAG). Can only
be activated by enabling TAG-OUT via parameter RMS.
Range of values: Not activated / activated
Basic setting: Not activated
Inputs from other logic (not I/O type inputs)
Name Description
SQ Group alarm acknowledgement
BL/OM Block OM operating
BL/AP Block alarm protection command
A/ON Auto command on
A/OFF Auto command off
SGC Under voltage limit signal
P/ON Protection command on
P/OFF Protection command off
EN/ON Enabling on
EN/OFF Enabling off
VOS Local controlling
AUTO Priority switch man/auto
MAN Priority switch auto/man
FB/OFF Feedback off
SGF Switchgear fault
FB/ON Feedback on
ANB Feeder not ready for operation
Training Center
Copying of this document, and giving it to others and use or communication of the contents, are forbidden without express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.
17

Table of Contents

Related product manuals