Reject to manual (REJ/MAN) 
Name: REJ/MAN 
Function: Defines whether the operation mode set to manual in the event of a 
fault or failure. Can only be activated by enabling TAG-OUT via parameter RMS. 
Range of values:   Not activated / activated 
Basic setting:   Not activated. 
 
Operation mode (OP_MODE) 
Name: OP_MODE 
Function: Defines the possible operating modes. Can only be activated by 
enabling TAG-OUT via parameter RMS. 
Range of values:   AUTO / MAN 
   SEMI 
   SEMI / MAN 
Basic setting:   AUTO / MAN. 
 
Behavior on switchgear fault (BSFG) 
Name: BSFG 
Function: Defines whether it is possible to initiate a manual “OFF” command from 
OM650 while the switchgear, breaker or motor starter is in fault (SAG). Can only 
be activated by enabling TAG-OUT via parameter RMS. 
Range of values:   Not activated / activated 
Basic setting:   Not activated 
 
 
Inputs from other logic (not I/O type inputs) 
Name Description 
SQ  Group alarm acknowledgement 
BL/OM Block OM operating 
BL/AP  Block alarm protection command 
A/ON  Auto command on 
A/OFF  Auto command off 
SGC Under voltage limit signal 
P/ON  Protection command on 
P/OFF  Protection command off 
EN/ON Enabling on 
EN/OFF Enabling off 
VOS Local controlling 
AUTO  Priority switch man/auto 
MAN  Priority switch auto/man 
FB/OFF Feedback off 
SGF Switchgear fault 
FB/ON Feedback on 
ANB  Feeder not ready for operation 