TXP CLC Course
5
YN - Status display computer, criteria Indication
The application area YN is used for group, subgroup, and sub-loop controls. The
serial numbers are assigned sequentially for each step. The signals in this
application area are created to indicate missing criteria for a particular step. An
additional character "K" is used to indicate that a message will be printed out on
the alarm printer if the criteria is missing.
XS - Step signals from a functional group control
The step signals within this group represent step numbers within a functional
group using sequence control. The step signals are divided into two groups, they
are:
XS01 - XS49 Startup program
XS51 - XS99 Shutdown program
Training Center
Copying of this document, and giving it to others and use or communication of the contents, are forbidden without express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.
31