TXP CLC Course
Application Code
The KKS system incorporates an application code which allows the consistent
identification of application or command signals. The application code is a suffix
of the KKS code, which identifies the application of the signal being created.
Application Code
11 MBV41 AA001 Y B 22
Serial Number
Application Area
Initial Character
Unit
Function Code
Equipment Code
Figure 7 - Application Code
Initial Character
There is only one application code, which is Y.
Application Area
The application area of the application code is used to identify the signal
assignment.
YA Function group control, sub-loop control
YB Control interface
YC Conventional closed-loop control
YJ Unspecified applications, i.e. a black box
YK Protection systems
YL Control room and control stations
YN Status display computer, criteria indication
YP Supervisory computer
YQ Analog signals
YR Major closed-loop control, in addition to YB and YT
YT Turbine instrumentation and control
YV Protective logic
YW Hard-wired alarm system