The signals RME, RMA, and SAG can be configured as either a NO or NC
contact
If the following signals are not wired, the function block reads them as follows:
SAG = “0” (not faulty) Parameter “RMS” set for NO contact.
ANB = “0” (ready or racked in)
RME = not RMA
RMA = not RME
When Feed-backs are not wired the command outputs are used for the
generation of the feed-back messages as follows:
RME = ALE
RMA = ALA
Depending on the operating voltages used, the following SIM modules can be
used in conjunction with the DCM function block:
SIM inputs:
321-1BL00-0AA0 32 x DC 24V Motor/Solenoid valve inputs
321-1BH01-0AA0 16 x DC 24V Motor/Solenoid valve inputs
321-1EH01-0AA0 16 x AC 120V Motor/Solenoid valve inputs
321-7BH00-0AB0 16 x DC 24V with sensor supply and diagnostics for
Motor/Solenoid valve inputs
SIM outputs:
322-1BL00-0AA0 32 x DC 24V / 0.5A Motor/Solenoid valve outputs
322-1BH01-0AA0 16 x DC 24V / 0.5A Motor/Solenoid valve outputs
322-1HH00-0AA0 16 x REL AC 120V / 0.5A Motor/Solenoid valve outputs
322-1HF01-0AA0 8 x REL AC 230V / 0.5A Motor/Solenoid valve outputs