In normal operation, the AT references the value of the input signal from the
Process Image Input Table (PAED), conditions it and writes it into the status data
block (ZUDB).
The signal must be defined (SIGDEF) on the individual level logic diagram
(function plan / YFR) that is identified with the Power Plant Identification Code
(KKS) for the equipment. The signal is then available for use in the AP. The
SIGDEF and KKS must match the input channel identifier in the parameter mask
of the SIM module on the rack level location drawing for the connection to the
input point.
Outputs to other Logic Diagrams
Name Description
AI/SIG Analog input signal
GS1 Limit signal 1
GS2 Limit signal 2
GS3 Limit signal 3
GS4 Limit signal 4
KSIM Analog input signal simulated
KG Analog input signal ok
Inputs from other Logic Diagrams
Name Description
KORR Correction factor
The KORR input port is used in conjunction with the MOD parameter (see
parameters) to input a multiplication factor for correction calculations.