There are some modifications that cannot be transferred online:
PB packaging: adding new diagrams to a loaded PB. It is possible to
delete functions from an existing PB-package, but not add new ones
online
Installation or removal of function blocks, which would cause relocation
into another processing frame. However, shifting function from one time-
controlled cycle to another is possible
Possible, but risking the occurrence of malfunctions, is the downloading of
following modifications:
Disconnection without reconnecting signals at function modules
Deletion of module channels
Cycle time modifications i.e. changing the running cycle of any
loaded PB