TXP-CLC Course
OT
OT
Terminal bus
Terminal bus
AS
AS
Time synchronization throughout DCS
by using Industrial Ethernet
PU
PU
SU
SU
OT
OT
DS
DS
ES
ES
OT/DT
OT/DT
AS
AS
Plant bus
Plant bus
OT/ET
OT/ET
time transmitter
time transmitter
transm
transm
. clock
. clock
every
every
10sec
10sec
GPS/DCF
GPS/DCF
trans
trans
mitter
mitter
In TXP, a system-wide, uniform time is kept by a time transmitter, from which
time-tags are obtained for marking events. The time-of-day is distributed via the
time transmitter over the plant bus.
The time-of-day transmitter is used for time synchronization of the TXP
subsystems AS620, OM650, and DS670 and it transmits time-of-day messages
over the plant bus at intervals of 10 seconds which are received and evaluated
by the connected TXP participants.
The time-of-day transmitter is only implemented on the plant bus; time is
transferred to the participants connected to the terminal bus via the PU. The
time-of-day transmitter can be synchronized via other clocks or it can be used to
synchronize other clocks.
Time-of-day synchronization can also be implemented via one of the
communications processors in the AS620 subsystems (CP1430).
Training Center
Copying of this document, and giving it to others and use or communication of the contents, are forbidden without express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.
6