Communication via SIKONETZ 5
AP10S
Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 31 of 48
6.9.16 1Bh: Counting direction
The counting direction can be set via parameter 1Bh.
Parameter address
1Bh
Description
counting direction
Access
rw
EEPROM
yes
Programming mode
yes
Data type
UNSIGNED 8
Default
0
Data content
MS500H
0: positive counting direction
1: negative counting direction
GS04
Bit 1
0: clockwise sense of rotation I (CW)
1: counter-clockwise sense of rotation E (CCW)
MS500H:
Positive counting direction: ascending position values when sensor moves to the sensor
cable
Negative counting direction: ascending position values when sensor moves away from the
sensor cable
GS04:
I sense of rotation: ascending position values with clockwise shaft rotation (CW, view on the
display)
E sense of rotation: ascending position values with counter clockwise shaft rotation (CCW,
view on the display)
6.9.17 1Ch: Resolution or measurement steps per revolution
When using an MS500H, the resolution is set in nm (nanometer) via parameter 1Ch. When
using a GS04, the number of measuring steps per revolution (display / revolution = APU) is
set.
Parameter address
1Ch
Description
MS500H: Resolution
Access
rw
EEPROM
yes
Programming mode
yes
Data type
UNSIGNED 32
Default
10000
Data content
310 … 2114064575