Communication via SIKONETZ 5
AP10S
Date: 04.09.2017 Art. No. 87826 Mod. status 269/17 Page 45 of 48
6.9.52 D0h: Response delay
Number of internal program cycles deferred before responding to a SIKONETZ5 bus telegram.
The response to a telegram can be delayed until the master is ready to receive. The value 10
corresponds to a delay of approx. 5 ms.
Parameter address
D0h
Description
Response delay
Access
rw
EEPROM
yes
Programming mode
yes
Data type
UNSIGNED 8
Default
0
Data content
0 … 20
6.9.53 D2h: Auto-ID assignment
See chapter 6.8: Auto-ID.
Parameter address
D2h
Description
Automated assignment of a node address
Access
wo
EEPROM
yes, the node number is stored with its adoption
Programming mode
no
Data type
UNSIGNED 8
Default
-
Data content
1 … 31
6.9.54 FAh: Status word
The status word can be read via this parameter. Bit 4: "Target window1 static" is deleted in
the status word with this operation. With this function, it can be detected whether the actual
position was ever in the target window even if this is not the case at present (see chapter
6.3.5: Status word)
Parameter address
FAh
Description
Read status word and delete "Target window1 static"
Access
ro
EEPROM
no
Programming mode
no
Data type
UNSIGNED 16
Default
-
Data content
0