5-7
Power Supply Wiring Distances, Continued
Table 5-2 lists the maximum distances from the NAC terminal block to the last appliance
in a Class B (string) configuration, depending on wire gauge and current. Use Table 5-2
to calculate wire distances for your application if you are using Class B wiring.
Table 5-2. Class B (string) Wiring Distances
Alarm
Current @
24V
0.75 mm
2
1.00 mm
2
1.50 mm
2
2.50 mm
2
4.00 mm
2
DC
Resistance
0.25A
230m
310m
460m
770m
1200m
12.0 ohms
0.50A
120m
150m
230m
380m
620m
6.0 ohms
0.75A
77m
100m
150m
260m
410m
4.0 ohms
1.00A
58m
77m
120m
190m
310m
3.0 ohms
1.25A
46m
62m
92m
150m
250m
2.4 ohms
1.50A
38m
51m
77m
130m
210m
2.0 ohms
1.75A
33m
44m
66m
110m
180m
1.7 ohms
2.00A
29m
38m
58m
96m
150m
1.5 ohms
2.25A
26m
34m
51m
85m
140m
1.3 ohms
2.50A
23m
31m
46m
77m
120m
1.2 ohms
2.75A
21m
28m
42m
70m
110m
1.1 ohms
3.00A
19m
26m
38m
64m
100m
1.0 ohms
Notes:
Max Distance = distance from SPS to last appliance.
This table is calculated at 49 degrees Centigrade.
Distances are based on a 3V drop, and take into account the worst-case panel
output voltage. These distances are based on the worst case of having one single
load at the furthest point.
If circuit integrity wire is used instead of housing cable in a fire rated enclosure,
reduce wiring distances by 12 m for every 3 m of potential exposure.
Class B NAC
Wiring Table

Table of Contents

Other manuals for Simplex 4100ES-S1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100ES-S1 and is the answer not in the manual?

Simplex 4100ES-S1 Specifications

General IconGeneral
BrandSimplex
Model4100ES-S1
CategoryControl Panel
LanguageEnglish

Related product manuals