5-13
Using T-GEN 50 with 4100ES-S1, Continued
Table 5-4 shows the switch and link settings for T-GEN 50 software version 1.7 when
controlling from a NAC output.
Table 5-4. T-GEN 50 Settings
Alert to Evacuate
Change-Over Time
SW1
(T0)
SW2 (T1)
SW3
(T2)
Setting on T-GEN 50
OFF
OFF
OFF
0 sec
ON
OFF
OFF
30 sec
OFF
ON
OFF
1 min
ON
ON
OFF
1.5 min
OFF
OFF
ON
3 min
ON
OFF
ON
5 min
OFF
ON
ON
10 min
ON
ON
ON
Alert Only
SW1 to SW3 settings have no effect on Slave T-GEN 50s.
SWITCH
Name
Setting on T-GEN 50
SW4
ALM I/P
Supervision
OFF (Supervision disabled)
SW5
ALM I/P
OFF (Non-latching)
SW6
Evac Tone
OFF
SW7
OFF for AS 2220 tone
ON for ISO 8201 + Keywords
SW8
Evac Message
OFF for Evac Message 1 or Field
Recorded message,
ON for Evac Message 2 or Keywords
only in ISO 8201
Link
Name
Setting on T-GEN 50
1
BIAS
Can be FITTED if PA or Background
Music not required
2
MASTER
FITTED
3
REC EN
Fit to record message.
4
TEST
Fit for test tone during installation
5
SLAVE
NOT FITTED
6
SLAVE / MASTER
MASTER
7
FAULT=
DEF-/RELAY
RELAY
Continued on next page
T-GEN 50 Settings for
NAC Operation

Table of Contents

Other manuals for Simplex 4100ES-S1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100ES-S1 and is the answer not in the manual?

Simplex 4100ES-S1 Specifications

General IconGeneral
BrandSimplex
Model4100ES-S1
CategoryControl Panel
LanguageEnglish

Related product manuals