Reading out, provision and administration of PV system data
The ClusterController is the central communication unit for the system and continuously reads out
the data of the devices in the system (e.g. inverters, sensors). The ClusterController then makes this
system data available via the display, user interface and Modbus data interface. In addition, the PV
system data can be displayed, evaluated and managed using Sunny Portal.
Configuring device parameters
You can configure specific parameters of individual devices or entire device classes via the user
interface of the ClusterController. You must be logged into the user group Installer on the
ClusterController. The device parameters that can be configured, if any, depend on the device and
the rights of the user group. You may only change grid-sensitive device parameters
(SMAGridGuard parameters) with the approval of the grid operator and using your personal
SMAGridGuard code.
Sending e-mail alarms in the event of critical system statuses
You have the option of receiving prompt information on critical system statuses via e-mail. The
ClusterController automatically sends a notification if alarm-related events occur in the system.
Feedback on current total active power of the system
You have the option of being informed of the total active power currently generated by the system
via an analog current output signal.
Implementation and feedback of grid operator setpoints for active power
limitation and reactive power operation under grid management services
With the ClusterController, as part of grid management services you can implement different grid
operator setpoints for active power limitation and reactive power operation of your system. The
ClusterController can implement the setpoints using open-loop control or closed-loop control.
For ClusterController systems without self-consumption and with direct limitation of active power
feed-in, the operating mode Open-loop control is used. In this operating mode, the
ClusterController can receive the setpoints either in the form of digital or analog signals, or via
Modbus. The different types of signal source can be combined so that, for example, the setpoints
for the active power limitation are received as digital signals and the reactive power setpoints are
received as analog signals: For ClusterController systems with self-consumption, the operating
mode Closed-loop control is used. In this operating mode, you can regulate the active power fed
in by the system at the grid-connection point and limit it e.g. to a fixed percentage value. In
agreement with your grid operator, you can use the user interface of the ClusterController to
configure which setpoints of the ClusterController are to be transmitted to the connected inverters
depending on the respective signal. In addition, you can use a digital response contact or an
analog current output signal to inform the grid operator of the setpoints (if any) for active power
limitation and reactive power operation that are currently being used in the system.
3 Product Description
SMA Solar Technology AG
User Manual 13ClusterController-BA-en-15

Table of Contents

Other manuals for SMA CLUSTER CONTROLLER

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMA CLUSTER CONTROLLER and is the answer not in the manual?

SMA CLUSTER CONTROLLER Specifications

General IconGeneral
Data LoggingYes
DisplayLCD
Power Supply24 V DC
Remote MonitoringYes
Protection ClassIP20
Communication InterfacesEthernet
Product TypeController
ManufacturerSMA

Related product manuals