Problem Cause and corrective measure
The ClusterController does not send
any data to SunnyPortal.
The data transmission is incorrectly configured.
Corrective measures:
If the ClusterController is not yet registered in
SunnyPortal, register the ClusterController in
SunnyPortal (see Section11.1, page56).
Test the connection to SunnyPortal (see
Section11.5, page58).
Check the settings for SunnyPortal (see Section11,
page56).
An error has occurred in the LAN.
Corrective measures:
Check whether the network settings of the individual
network components are correct. Adapt the network
settings if required.
Check whether the network components are
defective or damaged. Replace defective or
damaged network components.
After replacement of the ClusterCon-
troller, two systems with the same sys-
tem name appear in SunnyPortal.
The system has been registered twice in SunnyPortal. The
new ClusterController logs into SunnyPortal with a new
system identifier. SunnyPortal creates a new system for
this system identifier, even if you have given the system the
same name.
Corrective measures:
Assign the system identifier of the old system to the
replacement device (see Section11.6, page59).
In the replacement device, enter the e-mail address of
a user who has administrator rights for the system in
SunnyPortal.
In SunnyPortal, delete the new system created by the
replacement device.
18.3 Restarting the ClusterController via the User Interface
1. Log into the ClusterController as Installer.
2. Select the ClusterController in the system tree and select the menu Settings in the device
menu.
3. Select the parameter group Device > System.
4. In the field Initiate device restart, select [Execute].
The ClusterController is restarted. The start-up procedure can take up to two minutes.
18 Troubleshooting
SMA Solar Technology AG
User ManualClusterController-BA-en-15108

Table of Contents

Other manuals for SMA CLUSTER CONTROLLER

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMA CLUSTER CONTROLLER and is the answer not in the manual?

SMA CLUSTER CONTROLLER Specifications

General IconGeneral
Data LoggingYes
DisplayLCD
Power Supply24 V DC
Remote MonitoringYes
Protection ClassIP20
Communication InterfacesEthernet
Product TypeController
ManufacturerSMA

Related product manuals