To regulate active power feed-in at the grid-connection point, perform the following actions in the
specified order. The exact procedure is described in the following sections.
Adjusting the settings for the active power gradient
Selecting measurement source of active power feed-in at the grid-connection point
Making settings for active power limitation
Adjusting the Settings for the Active Power Gradient
This setting is only required if the grid operator requires the system not to feed in active power.
Requirement:
You must have received a personal SMAGridGuard code (application form for the
SMAGridGuard code available at www.SMA-Solar.com, for further information on the
SMAGridGuard code, see Section15.5, page83).
Procedure:
1. Log in to the ClusterController as Installer.
2. Select the SMAGridGuard symbol ( ) in the status bar.
This opens the SMAGridGuard dialog.
3. In the field Individual access code, enter the personal SMAGridGuard code.
4. Select [OK].
The SMAGridGuard mode is activated. In the system tree, updating the symbols for
access rights (SMAGridGuard symbol and padlock symbol) can take up to two minutes.
5. Select the system in the system tree and select the menu Settings in the device menu.
6. Select the parameter group System & device control.
7. Select [Edit].
8. Select the group Inverter.
9. Enter the value 200 in the field Active power gradient.
10. Select [Save].
Selecting Measurement Source of Active Power Feed-In at the Grid-Connection
Point
Requirement:
A measurement source (e.g., EnergyMeter) must be available at the grid-connection point.
Procedure:
1. Log into the ClusterController as Installer.
2. Select the ClusterController in the system tree.
3. Select Settings in the device menu.
4. Select the parameter group Grid connection > Measured values > Measurements at
grid-connection point.
5. Select [Edit].
13 Grid Management Services
SMA Solar Technology AG
User ManualClusterController-BA-en-1566

Table of Contents

Other manuals for SMA CLUSTER CONTROLLER

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMA CLUSTER CONTROLLER and is the answer not in the manual?

SMA CLUSTER CONTROLLER Specifications

General IconGeneral
Data LoggingYes
DisplayLCD
Power Supply24 V DC
Remote MonitoringYes
Protection ClassIP20
Communication InterfacesEthernet
Product TypeController
ManufacturerSMA

Related product manuals