Chapter 3 Transport and Setting Up
3.3 Installation
HRS Series
3-30
Recommended piping circuit
Fig. 3-16 Recommended piping circuit
No.
Description
Size
Recommended
part no.
Note
1
Valve
Rc1/2
-
-
2
Valve
Rc1
-
-
3
Y-strainer
Rc1
#40
Accessory
Install either the strainer or filter. If foreign
matter with a size of 20 μm or more are
likely to enter, install the particle filter.
Filter
Rc1
20μm
HRS-PF005
4
Flow meter
-
-
Prepare a flow meter with an appropriate
flow range.
5
Valve(Part of
thermo-chiller)
Rc3/4
-
-
6
Y-strainer
Rc1/2
#40
-
Install either the strainer or filter. If foreign
matter with a size of 20 μm or more are
likely to enter, install the particle filter.
Filter
Rc1/2
20μm
-
The filter cannot be directly connected to the thermo-chiller. Install it in the user’s piping system.
Thermo-chiller
automatic fluid
fill port
Circulating fluid
outlet
Circulating fluid
return port
Overflow port
Tank drain port
To wastewater collection pit
Fluid supply
Users
equipment
1
2
2
2
1
2
4
3
5
6