Chapter 5 Display and Setting of Various Functions
HRS Series 5.4 Description of the Screen
5-31
Table 5.4-5 TEMP READY signal setting
No.
Indication
Item
Setting and selection
Setting range
(1)
High/
Low
Upper/lower
temperature
limit
[High]
Sets the upper
temperature limit for
circulating fluid SP.
+0.1 ºC to +10.0 ºC
+1.0 ºC
[Low]
Sets the lower
temperature limit for
circulating fluid SP.
-0.1 ºC to -10.0 ºC
-1.0 ºC
(2)
Ready/
Out Time
Stable
temperature
time/out
time
[Ready Time]
“TEMP READYsignal
is output when the set time
has passed after the
circulating fluid temperature
rises/drops within the range
of (1) “Upper/Lower
temperature limit.”
10sec to 9999sec
180sec
[Out Time]
“TEMP READYˮ is cleared
when the set time has
passed after the circulating
fluid temperature rises/drops
outside the range of (1)
“Upper/Lower temperature
limitin the “TEMP READY
condition.
0sec to 600sec
5sec
(3)
Alarm
Type
AL12 alarm
operation
Disabled
Operation continues
during the alarm
Operation stops
during alarm
(4)
Start Time
Start time of
AL12 alarm
monitoring
[Start Time]
Monitoring of “AL12: TEMP
READY alarmstarts when
the set time has passed
after the start of operation.
0sec to 9999sec
600sec
By default.