Chapter 5 Display and Setting of Various Functions
5.4 Description of the Screen
HRS Series
5-32
About TEMP READY function
The operation chart of “TEMP READYsignal is shown in Fig. 5-6 TEMP READY signal
chart.
[Example of setting]
(1) “HighUpper temperature limit: +2ºC and “LowLower temperature limit: -2ºC
(2) “Ready TimeStable temperature time: 300 sec and “Out Timeextra
temperature time: 200 sec
(3) “Alarm TypeAlarm operation (AL12): “WRN”
(4) “Start TimeStart time of alarm monitoring (AL12): 1000 sec
Fig.5-6 TEMP READY signal chart
Status (1): Start operation of the chiller.
Status (2): The temperature is in the "High/Lowrange, but no “TEMP READYsignal is generated
since “Ready Timeis set at 300 sec at this point.
Status (3): The 300 sec count for “Ready Timeis reset since the temperature is now outside of the
Low” range.
Status (4): The 300 sec count for “Ready Time starts since the temperature is now within the
“High/Lowrange.
Status (5): “TEMP READYsignal is generated at this point since the temperature remains in the
“High/Lowrange for 300 sec of “Ready Time.”
Monitoring of “TEMP READY alarm (AL12)starts at this point where 1000 sec of “Start
Timehas elapsed.
Status (6): “TEMP READYsignal output continues since the temperature is now back within the “Out
Timerange of 200 sec even though it was temporarily outside the “Lowrange.
Status (7): “TEMP READYsignal turns OFF when 200 sec has passed after the temperature rises
above the “Highrange. “TEMP READY alarm (AL12)is simultaneously activated.
Chiller
Operation
Stop
Circulating fluid set
temperature 20ºC
TEMP READY
signal
ON
OFF
(2)
300sec
(5)
200sec
(7)
Circulating fluid
temperature
(1)
TEMP
READY
alarm(AL12)
Generate
No alarm
Time
150sec
(3)
(4)
100sec
(6)
1000sec
TEMP READY
Alarm (AL12)
monitoring
ON
OFF
“HighUpper
Temperature limit
+2C
LowLower
temperature limit
-2C