Chapter 3 Transport and Setting Up
3.3 Installation HRS Series
3-14
3.3.6 RS-485 Communication wiring
Serial communication RS-485, operation start/stop, setting and reading of
circulating fluid temperature, and reading of alarm condition can be done by
remote control.
Refer to the Communications Operation Manual for more details.
Wiring of interface communication cable
z Connecting to PC
RS-485 cannot be directly connected to a normal PC. Use a RS-232C/RS485 converter which is
available on the market.
Be sure to follow the wiring procedure below for connecting multiple thermo-chillers.
z
Configuration of connection
One host computer : One thermo-chiller, or one host computer : N thermo-chillers.
(Max. 31 thermo-chillers can be connected.)
1
SD+
5
SG
9
SD-
SD+
SD- SG
Terminal
resistance
Master This product
(first slave)
1
SD+
5
SG
9
SD-
This product
second slave
1
SD+
5
SG
9
SD-
This product
31
st
slaves
Terminal
resistance120Ω
Fig. 3-9 Connection of RS-485
Tips
Both ends of the communication connection (the end nodes) need to be
connected to the host computer.
The terminal resistance of this product can be set by the operation display
panel. Refer to “5.18 Communication function”.
Be sure to shut off the breaker of the facility power supply (the user’s
machine power supply) before wiring.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRS012-A*-10-* and is the answer not in the manual?

SMC Networks HRS012-A*-10-* Specifications

General IconGeneral
BrandSMC Networks
ModelHRS012-A*-10-*
CategoryChiller
LanguageEnglish

Related product manuals