5.10 Anti-freezing function 
5.10.1 Anti-freezing function 
The product can prevent the circulating fluid from freezing during winter time. 
If there is a possibility of the circulating fluid freezing due to changes in the 
installation and operating environment (operating period and weather), set 
the protection in advance. 
z 
If the circulating fluid temperature falls below 3℃, the pump will start 
operating automatically. 
z 
The heat generated by the pump operation will warm up the circulating 
fluid. 
When the circulating fluid temperature reaches 5℃ or higher, the pump 
will stop operating automatically. 
z 
As a result, the circulating fluid maintains a temperature of between 3℃ 
and 5℃, preventing freezing. 
 
If the anti-freezing function is set, [RUN] lamp flashes for 2 sec. during 
waiting (pump does not operate). The [RUN] lamp flashes at 0.3 sec. 
intervals during the automatic operation of the pump. The default setting of 
this function is “OFF”. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
z  This function starts in stand-by condition (power supply switch is 
ON). 
z  Fully open the valve or manual bypass valve arranged by the 
customer so that the circulating fluid can circulate when the pump 
starts automatic operation. 
z  In extremely cold weather conditions, the heat generated by the 
pump as described above may not be enough to prevent freezing. 
z  During the automatic operation, the pump does not stop even if you 
press "RUN/STOP" key. 
z  In an emergency, stop operation by shutting off the power supply.