Chapter 3 Transport and Setting Up
HRS Series 3.3 Installation
3-9
3.3.3 Preparation and wiring of power supply cable
Preparation
1. Strip the sheath from both ends of the cable.
2. Disassemble the power supply connector. Attach crimp terminals (mounting screw dia.:
M3.5) to one end of the cable to crimp them to L, N, E inside of the connector, then
reassemble the power supply connector.
3. Connect the other end of the cable to a terminal (e.g. crimped terminal) that is
compatible to the secondary side of the earth leakage breaker.
Fig. 3-5 Power supply cable
Cable
Crimped terminal
(Prepared by customer)
[Accessory]
Power supply
connector
N
E (Earth)
L
L
E
N
Earth leakage
breaker
(Secondary side)
Crimp terminal 3pcs. Terminal screw is M3.5.
Prepare the crimp terminal which is suitable for the cable
diameter.
The electrical facilities should be installed and wired in accordance
with local laws and regulations of each country and by a person
who has knowledge and experience.
Check the power supply. Operation with voltages, capacities and
frequencies other than the specified values can cause fire and
electrical shock.
Wire with an applicable cable size and terminal. Forcibly mounting
with an unsuitable size cable may result in heat generation or fire
Plug
(Prepared by customer)
L
E
N

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRS012-A*-10-* and is the answer not in the manual?

SMC Networks HRS012-A*-10-* Specifications

General IconGeneral
BrandSMC Networks
ModelHRS012-A*-10-*
CategoryChiller
LanguageEnglish

Related product manuals