14 Control functions
14.1
Overview
The load output and relay outputs can be automatically switched by the following control functions:
Q Morning light function
Q Evening light function
Q Night light function
Q Excess energy control
Q Generator manager
Q Alarm (AUX 1 and AUX 2 only)
Q Timer 1 ... 4
The following applies to the control functions:
Q The operating mode can be set for each output ( ‘On’ /‘Off’ /‘Function controlled’ ).
Q An individual switch-off threshold for deep discharge protection of the battery can be set for
each output.
Q When a control function is switched off its setting is retained.
Q The switching times and thresholds of the control functions can be individually set for each
output.
Q The control functions for an output are logically ORed. This means:
Each control function can switch on the output independently of the other control func-
tions.
The output is switched off when all control functions have switched it off, or the deep
discharge protection is active for this output.