Chapter 7 Parameter Explanation
Shanghai Sigriner STEP Electric Co., Ltd.
- 130 -
Figure 7-34 Dead Time of Forward and Reverse Rotation
P71.07 function sets the PWM modulation mode. 0: 5-segment; 1: 7-segment; 2: < 30% rpm
7-segment, > 30% 5-segment; 3: SPWM mode.
PWM Carrier frequency (kHz)
Carrier frequency adjustment: When the sound of the variable frequency motor is too loud, the
carrier frequency can be increased to make the sound lighter, and the carrier frequency interval can
be adjusted by random PWM width.
Note: The default carrier frequency is related to the inverter power. The higher the power, the lower
the default carrier frequency. If it exceeds the default value, please derate for use.
Zero velocity threshold (Hz)
P71.22 sets the zero velocity threshold; the default value is 0.2 Hz, and it is considered as zero
velocity when the actual running frequency is lower than the set value.
Dead zone compensation mode
Forward rotation deadband
compensation (%)
Dead zone threshold coefficient
(%)
P71.21 supports two dead zone compensation modes.
P71.23 compensates the dead time of the transition between the opening and closing of the upper
and lower bridge arms in forward rotation, and the default value is 100%.
PWM modulation mode:
0: Underflow update
1:Overflow and underflow update