7.4.3 X2A: Motor temperature sensor A
The motor temperature sensor of axis A is connected to terminal X2A. All device types of the
SC6 drive controller have connections for PTC thermistors
. You can connect a maximum of two
PTC triplets to X2A.
Information
Note that the evaluation of the temperature sensor is always active. If operation without a
temperature sensor is permitted, the connections must be bridged on X2. Otherwise a fault is
triggered when switching on the device.
Information
Note that a temperature sensor does not have to be connected to terminal X2 for a
HIPERFACE DSL encoder. In this case, the temperature sensor signal is transferred together
with the encoder signal over connector X4.
Term. Pin Designation Function
7 | 8
7 1TP1+ PTC connection
8 1TP2−
Tab. 27: X2A connection description, A motor temperature sensor
Cable requirements
Motor connection Max. length of the power cable
Without output choke 50m, shielded
With output choke 100m, shielded
Tab. 28: Maximum cable length of the power cable [m]
7.4.4 X2B: Motor holding brake B
The brake of axis B is connected to X2B for double-axis controllers. Only X2A is available for
single-axis controllers. The connection description of X2B matches the X2A description.
7.4.5 X2B: Motor temperature sensor B
The motor temperature sensor of axis B is connected to X2B for double-axis controllers. Only
X2A is available for single-axis controllers. The connection description of X2B matches the X2A
description.