10
3
SYSTEMA EOLO RT rev. 09ENIT04052021
FEATURES
3.4 TECHNICAL SPECIFICATIONS
Description
U.M. BC 25 RT BC 35 RT BC 45 RT BC 55 RT BC 65 RT BC 85 RT
Appliance category
II
2H3P
II
2H3B/P
Appliance type
B
23
Maximum heat input (NCV) kW 22 32 43 52 63 86
Minimum heat input (NCV) kW 8 10 15 18 21 23
Efciency at maximum / minimum heat input % 95/106 95/106 95/106 95/106 95/106 95/106
Nominal gas consumption
at 15 ° C and 1013 mbar
methane G 20 m³/h 2,33 3,39 4,55 5,50 6,67 8,89
LPG - butane G 30 kg/h 1,73 2,52 3,39 4,10 4,97 6,62
LPG - propane G 31 kg/h 1,71 2,49 3,34 4,04 4,89 6,53
Supply pressure
methane G 20 mbar 20
LPG - butane G 30 mbar 30
LPG - propane G 31 mbar 37
Gas inlet diameter Inches 3/4" 3/4" 3/4" 3/4" 3/4" 1"
Exhaust pipe diameter mm 100 100 100 100 100 130
Maximum length of ue gas exhaust duct (B23) m 8 8 8 8 8 8
Supply V/Hz 3/N/PE 50Hz 400V
Nominal electrical power kW See tab. 3.3 on p. 12 and 13
Operating temperature (min ÷ max) (*) °C 0÷35 (-20÷40 optional)
Air ow m³/h 2.500 3.500 5.000 6.000 7.000 9.000
Useful pressure available Pa See tab. 3.3 on p. 12 and 13
Noise (1 meter from the luminaire) - standard version dB(A) 56 57 57 58 59 61
Weight in standard conguration (excluded exhaust duct) kg 220 250 380 400 430 590
Description UM
BC 100
RT
BC 120
RT
BC 150
RT
BC 200
RT
BC 250
RT
BC 300
RT
Appliance category
II
2H3P
II
2H3B/P
Appliance type
B
23
Maximum heat input (NCV) kW 105 125 155 210 260 315
Minimum heat input (NCV) kW 34 40 46 65 78 95
Efciency at maximum / minimum heat input % 95/106 95/106 95/106 95/106 95/106 95/106
Nominal gas consumption
at 15 ° C and 1013 mbar
methane G 20 m³/h 11,11 13,23 16,40 22,22 27,51 33,33
LPG - butane G 30 kg/h 8,28 9,86 12,22 16,56 20,50 24,84
LPG - propane G 31 kg/h 8,16 9,71 12,04 16,31 20,20 24,47
Supply pressure
methane G 20 mbar 20
LPG - butane G 30 mbar 30
LPG - propane G 31 mbar 37
Gas inlet diameter Inches 1" 1" 1"1/4 1"1/4 1"1/4 1"1/4
Exhaust pipe diameter mm 130 130 200 200 200 250
Maximum length of ue gas exhaust duct (B23) m 8 8 8 8 8 8
Supply V/Hz 3/N/PE 50Hz 400V
Nominal electrical power kW See tab. 3.3 on p. 12 and 13
Operating temperature (min ÷ max) (*) °C -10÷35 (-20÷40 optional)
Air ow m³/h 10.000 12.000 14.000 20.000 24.000 28.000
Useful pressure available Pa See tab. 3.3 on p. 12 and 13
Noise (1 meter from the luminaire) - standard version dB(A) 62 63 65 66 67 67
Weight in standard conguration (excluded exhaust duct) kg 620 650 840 940 1040 1290
Tab. 3.1 Technical data BC version appliances: modulating condensing
(*) The minimum operating temperature is -10°C, it is however possible to use the appliance with temperatures down to -20 ° C by applying the kit
LOW TEMPERATURE (optional). Specify when ordering the request for the assembly of the LOW TEMPERATURE Kit.