| Configuration
GB
Digital outputs available for selection cont'd
Interlock External fan
Control
Automatic indication about prohibited external fan control (i.e. if defrosting is
activated).
Circulation pump Heating/
Cooling/Extra controller
Start/Stop signal to the circulation pump of the Heating/Cooling/Extra controller.
Fan output PWM (Pulse-width modulation) signal and triac output are already pre-addressed to specific terminals and
cannot be changed, all other outputs are free for configuration by commissioning. Outputs are free to be used for any
purpose.
Digital outputs are restricted by signal type and physical number of connections.
An output function is only allowed to be used once. Already used and configured terminal is greyed-out in the menu for
output type selection.
Analog and digital outputs have a selection for Auto/Manual modes and an adjustable value for Manual mode.
Manual mode selection overwrites all system related automatic functions. Analog output adjustable manual value
range is 0–10V and digital output values On/Off.
Table 4 Overview of output configuration
Analog outputs Digital outputs
Output type
Auto/Manual
Value
Output type
Auto/Manual
Value
9.7.6.3 Components
Configuration of connected components.
Heat Exchanger
Choose heat exchanger type.
Available types: Rotating / Plate
Activate or deactivate passive house function if heat exchanger type Rotating is selected.
Options: Yes / No.
Choose bypass damper location if heat exchanger type Plate is selected. Default setting is based on unit type.
Supply / Extract
Set actuator type. Default setting is based on unit type.
Range: 0–10 V / 2–10 V / 10–0 V / 10–2 V.
Heater
Choose heater type. Each selection unlocks additional configuration options. Default setting is based on unit type.
Available types: None / Electrical / Water / Change-over.
Set actuator type. Default value is 0–10 V.
Range: 0–10 V / 2–10 V / 10–0 V / 10–2 V.
Set circulation pump temperature. Default setting is 10°C. This option is available if Water / Change-over heater
type is selected.
Range: 0–20°C.
Set circulation pump stop delay. Default setting is 5 minutes. This option is available if Water / Change-over heat-
er type is selected.
Range: Off / 1–60 min.
Cooler
Choose cooler type. Each selection unlocks additional configuration options. Default setting is None.
Available types: None / Water / Change-over.