32
| Configuration
GB
Setting
Manual RPM Flow (CAV)
Pressure
(VAV)
External
Airflow
measurement
unit.
%
rpm
l/s, m
3
/h, cfm
Pa %
P-Band
0–3000 rpm 0–500 Pa
Default setting: 150 Pa
I-time
-
Off / 1–240 sec.
Default setting: 5
sec.
Off / 1–240 sec.
Default setting: 5 sec.
Airflow level
settings for each
level: MAXIMUM
LEVEL, HIGH
LEVEL, NORMAL
LEVEL, LOW
LEVEL,
MINIMUM LEVEL
16-100% 500–5000 rpm
Sensor range (airflow unit)
0–100%
Manual Fan Stop turn on or off manual fan stop, this function enables manual fan stop from HMI. Default setting
is OFF.
Pressure
Sensors
configure sensor
voltage relation
to pressure.
Set value at
which fan alarm
occurs. Default
setting is None
- -
Supply air fan control sensor:
Pressure at 0V: 0-500 Pa, default
setting 0 Pa
Pressure at 10V: 0-2500 Pa, default
setting 500 Pa.
Extract air fan control sensor:
Pressure at 0V: 0-500 Pa, default
setting 0 Pa.
Pressure at 10V: 0-2500 Pa, default
setting 500 Pa
-
Set K factor for
supply air fan
and extract air
fan. Default
settings are
based on unit
type.
- - SAF K-Factor
range: 0–1000
EAF K-Factor
range: 0–1000
- -
Outdoor
Compensation
A purpose of this function is to reduce the ventilation intensity during cold outdoor periods in
order to increase the supply air temperature and to avoid freezing of the heat exchanger.
Compensation can be applied for the supply air fan (unbalanced airflow) or both supply and
extract air fans if unbalanced airflow is not allowed.
Function linearly reduces speed of the fan by a value set in Stop Compensation Value (range:
-50% to 0%, default 0 °C) from a fixed outdoor air temperature of 0 °C to temperature set in
Stop Compensation Temperature (range: -25 °C to 0 °C, default 0 °C).
For units with plate heat exchanger it is recommended to set the Stop Compensation Value
to -20% and Stop Compensation Temperature value to -5 °C.
For units with Rotating heat exchangers it is recommended to set the Stop Compensation
Value to -30% and Stop Compensation Temperature value to -25 °C.
Important
Changing the airflow type does not change P-band value automatically. P-band value have to be changed
manually after changing the airflow type.
Demand Control
Configure indoor air quality sensors. Once sensor(s) are configured, Demand Control function is activated by choosing
AUTO mode in home screen.
Activate or deactivate CO
2
sensor. Default setting is Off.
Set CO
2
sensor setpoint. Default setting is 800 ppm (parts per million in atmosphere). Normal atmospheric CO
2
con-
centration is 400 ppm. Range: 100–2000 ppm.
Set P-band, default setting is 200 ppm. Range: 50–2000 ppm.